 |  |  |  |  |  |  |  | - DN 40 - 300 PN 10 / 16
- With flanges acc. EN 1092 part 2
- Type VdS with body seat of brass with flanges acc. EN 1092 part 2
- Type ALV with mounted lifting device
- Face to face length acc. EN 558 part 1 Column 48
- Type K DN 80 to 300 PN 10 resp. 16 as wafer type design
- Face to face length acc. EN 558 part 1 Column 20 ( DN 250 and 300 column 16 )
- Requirements acc. PED 97/23/EU Art. 1 Chapt. 3 without CE-Marking, for water and potable water, tests acc. DIN 3230 part 4 for potable water
- Of cast iron with laminar graphite
- Flap of GGG 40, EPDM rubber lined acc. KTW recommendation
- Permissible operating temperature up to 60°C soft sealing
- Inside and outside with epoxy coating acc. KTW recommendation as well as W 270
- Suitable for all installation between horizontal and vertical upwards
- Flap with self closing tendency, low noise
|  | | | Technical data (pdf-file, 477kb) General Installation-, Operation- and Maintenance Manual (pdf-file, 629kb)
Installation-, Operation- and Maintenance Manual (pdf-file, 238kb) Pressure Drop Diagram PSA ELA® (pdf-file, 92,4 kb Poster PSA-ELA, PSA ELA K (JPG-file, 201KB) | |  |  |
|